Makale detayı · 2013 · article

Ambient and Forced Vibration Testing of a Reinforced Concrete Building before and after Its Seismic Retrofitting

ISSN0733-9445
YÖKSİS OpenAlex
Yıl2013
Atıf51OpenAlex
Atıf48Semantic Scholar · 1 etkili
Yüzdelik%89,2
FWCI2,571,00 = dünya ortalaması
Scopus (SJR)Q1
WoS (JCR)Q1

Veri kaynağı ayrımı

  • YÖKSİSYÖKSİS makale kaydı
  • YÖKSİS dergi adıJournal of Structural Engineering
  • Katalog eşleşmesi (ISSN)Journal of Structural Engineering
  • OpenAlexOpenAlex zenginleştirmesi (özet, atıf, konular)
  • Semantic Scholaratıf sayısı (OpenAlex ile birleştirilmez)

Özet

OpenAlex İngilizce

This paper investigates the effects of seismic retrofitting on the modal characteristics of a 6-story RC building located in Istanbul, Turkey. Ambient vibration surveys were carried out before, during, and after the retrofitting work, which took place between June and December 2010. The building was retrofitted via jacketing of columns, addition of structural walls, and construction of a mat foundation. These studies were complemented with data from forced vibration tests performed with an eccentric-mass shaker after the retrofitting work was completed. During retrofitting, partitions were demolished; as a result, the first modal frequency of the building decreased by 11%, based on the results of the ambient vibration survey. The ambient vibration survey also showed that the modal frequencies after the seismic retrofitting increased by almost 96%. During the forced vibration tests, the building was excited around its modal frequencies using an eccentric-mass shaker. It was found that the modal damping values increased with the amplitude of the excitation force.

Konular

Atıflar

OpenAlex cited_by_count. WoS veya Scopus atıf sayısı değildir; o kaynaklar için ayrı kolon yoktur.

51atıfOpenAlex · cited_by_count (önbellek / veritabanı)

Yerel katalogda bu makaleye atıf yapan 23 yayın (OpenAlex referans eşleşmesi; tam dünya listesi değildir).

  1. 2021 A period-height relationship for newly constructed mid-rise reinforced concrete buildings in TurkeyAtıf 32 · OpenAlex
  2. 2021 A period-height relationship for newly constructed mid-rise reinforced concrete buildings in TurkeyAtıf 32 · OpenAlex
  3. 2016 Effect of AAC Infill Walls on Structural System Dynamics of a Concrete BuildingAtıf 18 · OpenAlex
  4. 2022 Effects of Seismic Damage and Retrofitting on a Full-scale Substandard RC Building-Ambient Vibration TestsAtıf 17 · OpenAlex
  5. 2021 Effects of Seismic Damage and Retrofitting on a Full-scale Substandard RC Building-Ambient Vibration TestsAtıf 17 · OpenAlex
  6. 2021 Effects of Seismic Damage and Retrofitting on a Full-scale Substandard RC Building-Ambient Vibration TestsAtıf 17 · OpenAlex
  7. 2019 Assessment of engineering demand parameters through SHM for RC-structuresAtıf 10 · OpenAlex
  8. 2017 Field testing of substandard RC buildings through forced vibration testsAtıf 10 · OpenAlex
  9. 2017 Field testing of substandard RC buildings through forced vibration testsAtıf 10 · OpenAlex
  10. 2017 Laboratory Tests and Vibration Surveys for the Mechanical Properties of Infill WallsAtıf 9 · OpenAlex

Yazarlar

7
  1. SERDAR SOYÖZ BOĞAZİÇİ ÜNİVERSİTESİ 1
  2. Ertuğrul Taciroğlu 2
  3. KUTAY ORAKÇAL BOĞAZİÇİ ÜNİVERSİTESİ 3
  4. Robert Nigbor 4
  5. Derek Skolnik 5
  6. HİLMİ LUŞ 6
  7. ERDAL ŞAFAK 7